Selecting the Right Remove and Replace Option

Identifying the merits of the three sprinkler removal and replacement options

Option 1 for Ordinary Temperature Sprinklers: Remove/Plug/Replace

  1. Shut off and drain the system involving a sprinkler contractor
  2. Remove existing “ordinary temperature” sprinklers and discard
  3. Plug the pipe outlets in the treatment area where working
  4. Restore the system and perform the bed bug heat treatment
  5. When treatment is complete, shut off and drain the system
  6. Replace with new “ordinary temperature” sprinklers
  7. Restore the system

Option 2 for Ordinary Temperature Sprinklers: Remove/Replace/Replace

  1. Shut off and drain the system involving a sprinkler contractor
  2. Remove existing “ordinary temperature” sprinklers and discard
  3. Temporarily replace with “intermediate temperature” sprinklers in the treatment area
  4. Restore the system and perform the bed bug heat treatment
  5. When treatment is complete, shut off and drain system
  6. Replace with new “ordinary temperature” sprinklers
  7. Restore the system

Option 3 for Ordinary Temperature Sprinklers: Remove/Replace/Monitor

  1. Shut off and drain the system involving a sprinkler contractor
  2. Remove existing “ordinary temperature” sprinklers and discard
  3. Replace with “intermediate temperature” sprinklers in the treatment area
  4. Restore the system and perform the bed bug heat treatment
  5. Monitor the temperature at each sprinkler
  6. Replace sprinklers exposed to >150°F (requires shut off, drain, and restore)
  • If not exposed to 150°F, then leave the new sprinklers in place
  1. Leave the “intermediate temperature” sprinklers in place
  2. Note: With new standards in place, using ordinary or intermediate temperature sprinklers in life hazard areas are allowed at will

Option 4 for Intermediate Temperature Sprinklers: Remove/Replace/Monitor

  1. Perform the bed bug heat treatment
  2. Monitor the temperature at each sprinkler
  3. Replace sprinklers exposed to >150°F (requires shut off, drain, and restore)
  • If not exposed to 150°F, then leave the new sprinklers in place
  1. Leave the “intermediate temperature” sprinklers in place


Untuk keterangan lebih lanjut, silahkan download PDF ini :

Ulasan

/5
Ulasan
5
4
3
2
1

Foto dari Pembeli

Ulasan dari Pembeli

Filter
Semua
Dengan Foto
5
4
3
2
1
Telepon
Request a Quote
Produk Siap di Pesan
Rp 0
1
Bendera Indonesia Indonesia  |  Bendera Inggris English
Ingin menghubungi kami?
Klik tombol dibawah
Logo IDT
Chatbot